The Power Box TM Cable - 2491B / 6701B

The 2491B and 6701B Low smoke halogen free cableThe 6701B Low Smoke Halogen Free (formerly 2491B) LSHF flexible cable to BS 7211 is used in panel, conduit and general fixed wiring applications where there is a requirement for flexibility during installation and in the event of fire, a need to minimise the risk from smoke and toxic fumes but where circuit integrity is not required.

These cables emit less that 0.5% Hydrogen Chloride (HCI) in accordance with BS 6425 part 1 and IEC 60754 part 1.

Cable Conductors are a flexible Class 5 plain annealed stranded copper to BS 6360.

Cable insulation is low smoke halogen free (LSHF) compound type E1.5 to BS 7655 in accordance with BS 6425 part 1 (IEC 60754-1). Flame retardant to BS 4066 Parts 1 and 2 (IEC 60332-1)

Available in sizes 0.5 to 240.0 mm2

Cable insulation colours :-
Up to 6mm - black, red, brown, blue, white, grey, violet, pink, orange, yellow, green / yellow.
10 mm and above - Black only.

Voltage Rating :-
0.5 to 1.0 mm2 300/500V ac
1.5 to 240.0 mm2 450/750V ac

Operating temperature: -10oC to +90oC